For most of its history, Australia’s grid was stabilised by physics: the heavy spinning machines in coal and gas plants kept frequency steady and voltage firm as a by-product of running. As those plants retire, that free stability disappears — and batteries fitted with grid-forming inverters are the technology being asked to replace it. This article explains why inverter control, not just battery chemistry, is becoming the story.
The Problem: A Grid That Used to Stabilise Itself
Synchronous generators — the rotating machines in coal, gas, and hydro plants — have always done two jobs without being paid for either. Their spinning mass provides inertia, which resists rapid changes in frequency, and their electromagnetic response maintains system strength, which keeps voltage stable when faults occur. Solar farms, wind farms, and ordinary batteries do neither unless they are deliberately engineered to.
Australia is now losing that automatic stability. Roughly half of the remaining coal fleet is expected to retire by 2035, and renewables already meet more than 40% of NEM electricity. As the synchronous machines leave, the grid becomes electrically “weaker”: voltage sags more easily, frequency swings faster, and connecting inverter-based generators gets harder. AEMO’s 2025 Transition Plan for System Security warns of a tightening window — in New South Wales, the Eraring coal plant is slated to close in 2027, and any delay bringing new stability assets online could leave periods with inadequate voltage control. What was once a free by-product has become a deliberate engineering task.
Grid-Following vs Grid-Forming: What Actually Changes
The difference comes down to one question: does the inverter follow the grid, or does it help create the grid?
A grid-following inverter is the default technology in solar farms and conventional batteries. It uses a phase-locked loop (PLL) to track the voltage waveform of the network, then injects controlled current into that waveform. It works well on a strong grid — but as the grid weakens, the PLL that locks onto the waveform can start to oscillate, exactly the failure mode seen as synchronous generation declines.
A grid-forming inverter behaves like a small synchronous generator. Instead of tracking the grid’s voltage, it creates its own voltage and frequency reference and lets the grid synchronise to it through the natural exchange of power. That one architectural difference is what lets a battery provide the services that spinning machines used to provide for free.

| Grid-following (GFL) | Grid-forming (GFM) | |
|---|---|---|
| Reference | Tracks the grid’s voltage phase (PLL) | Creates its own voltage and frequency reference |
| Behaves as | Current source | Voltage source |
| In weak grids | PLL can become unstable | Holds voltage and frequency steady |
| System services | None by itself | Synthetic inertia, system strength, fast frequency response |
| Island / black-start | Needs a grid to follow | Can form a local island and restart it |
That is why 74% of the roughly 45 GW of battery projects in Australia’s connection queue have chosen grid-forming: on a grid where half the stabilising machines have left, grid-forming is what keeps the lights on.
Why Inverter Control Is the Difference Maker
Two batteries with identical cells and racks can behave completely differently — one passively follows the network, the other actively stabilises it — and the difference lives entirely in the inverter control software, which is why “inverter control” now matters more than battery chemistry.
Grid-forming control comes in two main flavours. Droop control is the simpler method: the inverter adjusts its power output in response to small changes in grid frequency, sharing load autonomously with other units without needing communication between them. Virtual synchronous machine (VSM) control goes further, emulating the swing equation of a physical generator — including its inertia and damping — inside the controller. VSM is widely seen as the most promising direction because it can be tuned by reprogramming controller parameters, giving the battery a synthetic inertia that mimics the coal plant it is replacing.
Because the difference is software, it is reversible and cheap. Origin ran its new Mortlake battery in grid-forming mode partly because the switch avoided system strength connection fees of A$2–3 million per year — mainly a software change rather than new hardware. And in the moments that matter, grid-forming responds in milliseconds, where a gas unit needs minutes to ramp.
ARENA Is Scaling Grid-Forming on Real Projects
Grid-forming is not a lab concept in Australia. The Dalrymple battery in South Australia was the country’s first transmission-connected grid-forming system in 2018; Hornsdale Power Reserve, Australia’s first big battery, was upgraded to full grid-forming in 2022; and the Riverina battery followed in 2023. The current wave is bigger, and ARENA is funding it deliberately.
The Gnarwarre BESS in Victoria is a 250 MW / 500 MWh project developed by FRV Australia, backed by an A$15 million ARENA grant to demonstrate advanced inverter capability. It reached financial close in August 2025 and will be commissioned with grid-forming functionality enabled — a large-scale battery, not a pilot, built to show that grid-forming batteries can reduce reliance on synchronous generators and inform how regulators procure these services.
The Mortlake BESS, developed by Origin Energy, is the commercial proof point. A 300 MW / 650 MWh battery beside Origin’s gas power station in south-west Victoria, it uses 116 grid-forming SMA inverters, began commercial operations in August 2026, and carries up to A$24 million in ARENA funding. AEMO has accepted grid-forming as a valid system strength remediation technology, and with the battery online Origin’s storage portfolio reached 1.3 GW / 4.1 GWh — batteries increasingly displacing its gas units at demand peaks.

What It Means for Developers and EPCs
The shift is becoming the default way Australia plans its grid. Transgrid’s preferred portfolio for New South Wales pairs synchronous condensers with about 5 GW of grid-forming batteries — roughly equivalent in system strength to 17 condensers — and expects the batteries to provide almost half of the state’s system strength requirement. In Queensland, Powerlink is planning synchronous condensers across the coal exit zone, while AEMO has contracted system strength from the Koorangie battery (185 MW / 370 MWh). The regulator AEMC has even rejected a real-time market for inertia, judging it too costly — stability is being procured through contracts and connection requirements instead of a spot market.
For companies that design, build, and operate energy systems, this is a concrete engineering demand signal:
– System strength is now a design deliverable, not an afterthought. Connection studies increasingly ask whether a battery can hold the grid steady, not just whether it can charge and discharge.
– Inverter and control specifications carry the engineering weight. Grid-forming performance — droop or VSM parameters, fault ride-through, black-start capability — is where the value lives, and where experienced control engineers earn their keep.
– Software-defined storage is the direction. The same physical hardware can be configured for grid-following, grid-forming, or both over time, which changes how projects are specified and how EPCs scope commissioning.
There is a healthy caveat. AEMO’s 2026 technical work is the milestone that will fully validate grid-forming behaviour for system strength, and synchronous condensers remain necessary in the meantime. But the direction is settled: as Australia’s rotating machines retire, the inverter is no longer just a power converter — it is becoming the device that holds the grid together.
FAQ
Q: What is the difference between grid-following and grid-forming inverters?
A: A grid-following inverter tracks the grid’s voltage with a phase-locked loop and injects current into it, while a grid-forming inverter creates its own voltage and frequency reference and behaves like a small synchronous generator — providing inertia and system strength.
Q: Why does Australia need grid-forming batteries?
A: Coal and gas plants have traditionally provided inertia and system strength as a free by-product; as they retire, grid-forming batteries are the main technology able to replace those stability services in a high-renewables grid.
Q: What is system strength?
A: System strength is the ability of the network to keep voltage stable when faults or load changes occur; it has historically come from synchronous machines and is now a scarce, engineered resource as they leave.
Q: Which Australian projects use grid-forming technology?
A: Dalrymple (2018), Hornsdale Power Reserve (upgraded 2022), and Riverina (2023) were early examples; the current wave includes Origin’s 300 MW / 650 MWh Mortlake BESS (operational August 2026) and FRV’s 250 MW / 500 MWh Gnarwarre BESS.
Q: Do grid-forming batteries need new hardware?
A: In many cases no — the switch between grid-following and grid-forming is largely software, which is why Origin avoided A$2–3 million per year in system strength fees by running its Mortlake battery in grid-forming mode.
YURI POWER Engineering Team · August 29, 2026